Product Specs
Generator Set Specifications
- Standby Rating
- 2250 ekW
- Prime Power Rating
- 1825 ekW
- Emissions/Fuel Strategy
- Low fuel, Low Emissions
- Voltage
- 380 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 2250 ekW
- Minimum Rating
- 1640 ekW
Engine Specifications
- Engine Model
- 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69 in
- Stroke
- 7.48 in
- Displacement
- 4210.64 in
- Compression Ratio
- 14.0:1
- Aspiration
- TA
- Fuel System
- MEUI
- Governor Type
- ADEM™ A4
Generator Set Dimensions
- Length - Maximum
- 234.5 in
- Width - Maximum
- 90 in
- Height - Maximum
- 98.2 in
- Dry Weight - Genset (maximum)
- 30310 lb
Standard Equipment
-
- Air Inlet System
-
- Air cleaner; single element canister type
-
- Control Panels
-
- PLC functionality
- Oil pressure (psi, kPa or bar)
- Text alarm/event descriptions
- KVAR/PF modes
- Cat connect
- Overspeed
- Amps (per phase & average)
- Programmable protective relaying functions:
- DC volts
- EMCP 4.2B
- Power factor (per phase & average)
- Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
- Load histogram feature
- Generator set packages include:
- Frequency (Hz)
- Emergency stop pushbutton
- Over/under voltage (27/59)
- RFI suppression
- 24 Volt DC operation
- Low coolant level
- Reverse power (kW) (32) - Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
- 4 Programmable relay outputs (Form A)
- Volts (L-L & L-N)
- Caterpillar's voltage regulator
- IVR includes:
- Auto/start/stop control
- kVA (per phase, average & percent)
- Lamp test
- Over/under frequency (81 o/u)
- Environmental sealed front face
- 3 Phase voltage sensing
- Engine cool
- kVAr-hr (total)
- Low oil pressure
- Accessory module data link
- Emergency stop
- Customer data link (Modbus RTU)
- Communications:
- Warning/shutdown with common LED indication of shutdowns for:
- 0 True RMS AC metering, 3-phase, +/-2% accuracy
- Digital indication for:
- Customizable screens
- Failure to start (overcrank)
- Serial annunciator module data link
- Coolant temperature
- Controls:
- Overcurrent (50/51)
- Number of I/O varies on options selected
- Reactive droop capability
- Low coolant temperature
- High coolant temperature
- Min / max exciter
- Alarm acknowledge
- RPM
- Generator phase sequence
- Limiter and exciter diode monitor
- Speed adjust
- Operating hours
- kW (per phase, average & percent)
- 3 Analog inputs
- Generator mounted - rear facing
- 6 Customer programmable digital inputs
-
- Lubrication System
-
- Oil filter, filler and dipstick
- Oil drain lines and valve
- Gear type lube oil pump
- Fumes disposal
- Lubricating oil
-
- Mounting System
-
- Rubber anti-vibration mounts - shipped loose
- Rails - engine/generator/radiator mounting
- Anti-vibration mounts (shipped loose)
-
- Starting System
-
- 45 Amp Charging alternator
- 24 Volt electric starting motor
- Battery and battery rack w/cables
- Battery disconnect switch
-
- Literature
-
- Parts book
- Operation & Maintenance Manual
Attachments
-
- Control System
-
- EMCP 4.3, EMCP 4.4
-
- Air Inlet System
-
- Dual element air cleaner
- Single element filter
-
- Cooling System
-
- Water level switch gauges
- Optional installed ATAAC radiators
- Standard ambient ATAAC radiators
- Standard ambient radiators
- Coolant
- Optional installed radiators
-
- Crankcase System
-
- Explosion relief valves
- No explosion relief valves
- Ventilation system
-
- Exhaust System
-
- Elbows
- Flange and exhaust expanders
- Tier 4 clean emissions module
- Tier 4 clean emission MOD Kits
- Clean emission parts
- Exhaust offset
- Mufflers
- Tier 4 dosing cabinet
- Flanges
- Flexible fittings
- Y Adapters
-
- Fuel System
-
- Fuel priming pumps (Tier 4) - Manual or electric
- Primary fuel filter
-
- General
-
- US aid emblem
- Special paint (Colors other than Caterpillar yellow or high performance paints)
-
- Generators And Attachments
-
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
- Generator conversion
- Differential current transformers (DCT)
- Differential current transformers (DCT) 8.7 kV and 15 kV classes
- Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
- Thermostat for space heater
- Space heater
- High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
- Alternator air cleaner
- High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
- Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
-
- Instrumentation
-
- Pyrometer and Thermocouples
-
- Lubrication System
-
- Oil level regulator
- Prelube pumps
- Lube oil in standard sump
-
- Mounting System
-
- Puck style low efficiency isolators
- Spring type vibration isolators
- IBC vibration isolators
-
- Power Connections
-
- Right side power connections
- Ground cables between generator and terminal box
- Neutral ground connections
- Low voltage Circuit breakers
- 2700 Frame, four lead, four terminal
- Rear power connections
- Left side power connections
- Center post busbars
-
- Special Tests / Reports
-
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
- Fuel consumption test
- Canadian Standards Association certification
- Torsional vibration analysis reports
- IBC Certification
- Generator test report
- Generator set fuel consumption test
- OSHPD Certification
- Standard engine test charge
-
- Starting And Charging
-
- Engine barring device
- Air pressure regulator
- Starter cover
- Electric starting motors
- Jacket water heaters
- Air starting motors
- 24 Volt battery set - Dry
- 10, 20, 35 and 50 Amp Battery chargers
-
- Extended Service Coverage
-
- Platinum, Gold and Silver coverage