Product Specs
Generator Set Specifications
- Voltage
- 240 Volts
- Frequency
- 60 Hz
- Natural Gas/LPG Rating
- 60 ekW / 60 ekW
- Emissions/Fuel Strategy
- U.S. EPA Certified for Stationary Emergency Application
- Speed
- 1800 rpm
- Natural Gas Rating
- 60 ekW / 60 ekW
Engine Specifications
- Engine Model
- 5.7L V8, 4-cycle Gas
- Displacement
- 350 in
- Fuel System
- Natural Gas / LP Vapor
- Aspiration
- Natural Aspiration
- Governor Type
- Electronic
- Compression Ratio
- 9.4:1
- Bore
- 4 in
- Stroke
- 3.48 in
Generator Set Dimensions
- Length
- 83.3 in
- Width
- 39.4 in
- Height
- 53.5 in
- Weight
- 2110 lb
Standard Equipment
- 
            
            - Air Inlet
- 
                        - Single element air filter
 
 
- 
            
            - Cooling
- 
                        - Radiator and cooling fan complete with protective guards
- Standard ambient temperatures up to 50°C (122°F)
 
 
- 
            
            - Exhaust
- 
                        - Exhaust outlet with 3” pipe
 
 
- 
            
            - Fuel
- 
                        - NPT connection
- Natural Gas or LP Vapor
- Dual lock off valves
 
 
- 
            
            - Generator
- 
                        - Integrated Voltage Regulator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
 
 
- 
            
            - Governor
- 
                        - Electronic governor (non adjustable)
 
 
- 
            
            - Control Panel
- 
                        - EMCP 4.2 Series generator set controller
 
 
- 
            
            - Mounting
- 
                        - Rubber vibration isolators
 
 
- 
            
            - Starting/charging
- 
                        - Batteries with rack and cables
- 12 volt starting motor
 
 
Attachments
- 
            
            - Generator
- 
                        - Oversize and premium generators
- Excitation: [ ] Permanent Magnet Excited (PM)
- Anti-condensation heater
 
 
- 
            
            - Starting/charging
- 
                        - Battery heater
- Lube oil sump heater
- Jacket water heater
- Battery charger – UL Listed 10 amp
 
 
- 
            
            - General
- 
                        - CSA Certified
- Suitable for Use as Service Equipment (SUSE)
- Enclosures: sound attenuated, weather protective
- UL 2200 Listed
- Automatic transfer switches (ATS)
 
 